Saytu xam-xam bi jëm ci natt CT PT

 Jul 10, 2026

 Bayil ab bataaxal

 

Bu ñuy saytu transformatër bi, muy ingenieur kuuraŋ, mën nañu daje ak jafe-jafe yu bari ci liggéey bi. Ci laaj ak tontu yi ci topp ci wàllu natt CT PT, mën nanu am xam-xam ak leeral yu am solo lool.

 

FAQ 1: Luy Juumte Ratio, ak lu tax 0.2s Class CTs dañu tar nii?

Q: Jumtukaay ratio bi 0.05%? Lan moo waral CT biy jëfandikoo meter dafa wara gëna dëggu CT biy aar?

A: Jumtukaayu ratioo mooy % wuute gi am ci digganté plaque de nom ak natt. 0.2s dafay tekki "Special" njubte wàcci ba 1% courant. Dafay wax ci "Njub" ci faktiiru kuuraŋ bi.

FAQ 2: Polarite - "Veto" bi ci Aar bu wuute

Q: Lan mooy xew sudee sama ratio baaxna waaye polarite (S1/S2) dafa soppiku?

A: Sistemu aar bi dina def "Suicide." Relay bi dina gis courant fault bu rëy.

Logique différentielle (87 Relais):

• Polarite bu jaar yoon: 100A Ci biir - 100A Ci genn=0A wuute. ✅

• Polarite buñ delloo: 100A ci biir - (-100A ci biti)=200A wuute. ❌

• Resultat: Njuumte ci saasi. Mën nga jox kuuraŋ gaaraas bi.

FAQ 3: Deplasement fase (Njuumte ci angle) ak faktiiru kuuraŋ

Q: Lan moo waral "Njuumte Faas" bu ndaw (misaal . 15 simili) am solo sudee magnitude bi jub na?

A: Ndax doole aktiif P=V * I * cos (phi). Deplasement fase dafay soppi waxtu vague courant bi.

Fiir bu jaar yoon:

• Metre yi ñooy natt ANGLE bi diggante V ak I.

• Sudee -puissance-facteur yu néew (misaal cos phi=0.5), njuumte 15 simili dafay jur njuumte 1% ci puissance.

FAQ 4: Xeetu modelaasioŋ - xool 1000A ak 120V kese

Q: Test yi fi yàgg a nekk dañuy push 1000A ci primaire bi. Analyser bi mën na nekk lu jaar yoon te amul?

A: Dafay jëfandikoo "Njàngalem Model." Dafay tàqale geometrie physique (wiir) ak perte magnetik.

Ni muy doxee:

❶ Rasio wërsëg: Pont voltage bu kawe-natt Ns/Np.

❷ Modèle magnétique: Courbe excitation dafay wane bu baax ba ñaata courant la core fer bi "sàcc."

❸ Xalaatal Math: Ordinatër bi dafay boole Turns + Loss + Burden ngir wax luy waaja am ci 1000A njuumte.

FAQ 5: Koolute ci terrain - 0.1% njub ci benn substation bu bari bruit

Q: Ndax jafe-jafe yi ci substation du yàq natt bu jaar yoon bu 0.1%?

A: Analyseur yi dañuy jëfandikoo segg numérique bu sew - ak coppite fréquence ngir baña noppi.

Pexe ngir baña nangu bruit:

• Coppite fréquence: Dafay dugal siñaal ci 49.7 Hz wala 50.3 Hz. Dafay baña bàyyi xel ci bruit bi ci ginaaw 50 Hz.

• Royuwaay bi ci biir: Self-dafay kalibre ci royuwaayi voltage bi ci biir bu ultra-stabil.

• Kelvin 4-Fiil: Dafay dindi mbañeelu sa fiil test.

Yonnee nga laaj
Yonnee nga laaj