Q1: Lan moo waral ñu yokk ñaari yoon fréquence (150Hz ba 200Hz) ci test PD yiñ indi ci transformatëru 40 MVA?
A: Sudee dañuy saytu isolation longitudinaal bu transformateur bi (inter-tour ak inter-couche), danuy jëfandikoo voltage bu ëpp bu baax valeur nominal bi (daanaka 1.5x). Sudee danuy jëfandikoo ab balluwaay bu 50Hz/60Hz, core wen wi dafay dugg ci saturation magnetik ci saasi, loolu mooy waral courant excitation bi di yokk bu baax ba noppi yàq enroulement yi. Sunu sukkandikoo ci formul flux magnétik (Φ=U/4.44fNΦ{9}}U/4.44fN), suñu yokkee fréquence bi ba 150Hz wala 200Hz, dina nu mëna am voltage test bu yéeg boole ci tëye flux core bi ci niveau bu wóor, bu amul saturation.
Q2: Nan lañu mëna def ba yegg ci niveau bruit bu < 10pC ci test transformateur 66kV ci barab bi?
A: Ngir mëna wàññi bruit bu mel nii ci biir tool fàww nga am gis-gis bu lalu ci sistem:
Seggal hardware: Jëfandikoo ab Source de puissance bu am fréquence bu mën soppiku ak ab filtre LC bu diis ngir moytu bruit bu fréquence bu kawe biy joge ci commutation IGBT.
Optimisation ci champ électrique bi: Def ab bouclier bu am diametre bu mag (Bague Corona) ci kaw bushing yi 66kV ngir dindi corona air bi.
Logique de terre: def sistem de terre bu am benn -poñ ngir moytu boucles de terre yiy nekk antenne ngir EMI.
Cable: Jëfandikoo ñaari -fiil natt yu am kaaraange ngir aar siñaal PD yu xarañ yi ci jafe-jafe yi am ci biir.
Q3: Lan mooy tegtali jàll/jàllul ngir test PD trafo 66kV buñu sukkandikoo ci IEC 60076-3?
A: Ngir transformatër yu am Um{0}} kVUm =72.5 kV (klaas 66kV), dañuy laaj ni ci diiru monitëru voltage bu yàgg (li gëna bari ci 1.5Um/31.5Um/3), niveau decharge bi dafa wara nekk ci suufu 100pC. Li gëna am solo mooy tendaas PD dafa wara dëgër; bépp yokkute bu wéy ci magnitude decharge wala viteesu puls ci diiru 30-60 simili test bi dañu koy jàppee ni njuumte, doonte valeur absolu bi mingi ci suufu 100pC.
Q4: Ndax mën naa jëfandikoo transformatëru test Hipot AC buñ miin ci palaasu sistemu fréquence buy soppiku?
A:Transformatëru test buñ miin mën na defTest buy muñ Source bu tàqaloo(isolation bu mag ci suuf). Waaye, noonu lajaarul yoonngir ñi gëna am soloTest voltage induitci kaw benn aparey 40MVA ndax mënul joxe fréquence bu gëna yokk (150Hz+) ngir moytu saturation core. Rax ci dolli, transformatër yiñ daan faral di def test dañu diis lool te jafe nañu yóbbu ci sous-station yu 66kV yu sori, soo koy méngale ak sistem modulaire yu am fréquence variable.
Q5: Lan mooy njariñu jëfandikoo bibliotek emprent PRPD 2D/3D ci losisel biy saytu feebar bi?
A: Fase - Bibliothèque Decharge Partielle Résolue (PRPD) dafay may ingénieur yi ñu mëna dem fu ëppu li ñuy am ci "Pass/Fail". Soo méngale motif decharge yi (forme, position fase, ak fréquence) ak base de done yu am fi yaxxu, sistem bi mën na xàmmee ci saasi xeetu fi yaxxu - lu melni protrusion bu ñaw ci kaw conducteur bi, particule metalik buy féey ci biir diw gi, wala benn void ci isolation bu dëgër bi. Bii "Sistem Expert" dafay wàññi bu baax risku njuumti nit ñi ci jàngat done yi ci barab bi.