Q: Buñu joxee P0 ak P0 ci test yi, naka laa mëna xaymaa efficacité ci niveau de charge yu wuute?
A: Gaawaay η=P_génn / (P_génn + P0 + 2 × P6) × 100%, fu=facteur de charge.
Ci misaal: Trafo 10 MVA, P0=12 kW, P6=85 kW:
|
Diisaay natt |
|
Sortie (kW) |
P0 (kW) |
2×P6 (kW) |
η (%) |
|
25% |
0.25 |
2,500 |
12 |
5.3 |
99.31 |
|
50% |
0.50 |
5,000 |
12 |
21.3 |
99.34 |
|
75% |
0.75 |
7,500 |
12 |
47.8 |
99.21 |
|
100% |
1.00 |
10,000 |
12 |
85.0 |
99.04 |
|
120% |
1.20 |
12,000 |
12 |
122.4 |
98.89 |
Gaawaay bi gëna mag ci=√(P0 / P6)=0.376 → ~37.6% sargal.
Norm yiñ tëral ngir sakkanal kuuraŋ:
• IEC 60076-20: Klaas EEI A (gëna kawe) → D.
• Ecodesign 2019/1783: Ñaareelu dayo (2021), Ñatteelu dayo (2025–27).
• DOE 10 CFR pàcc 431: sàrt bu bees buy tàmbali liggéey ci weeru suwe 2026.
• GB 20052-2020 (Chine): Njàngale 1 (gëna kawe) → 3.
• IS 1180 (Inde): BEE 1 ba 5.
Xeetu TCO: TCO=Njëgg + A × P0 + B × P6
≈ $3,000–8,000/kW (amul njëg buñ kapitalise).
B ≈ $500–2,000/kW (jëg buñ kapitalise).