naka lañuy xaymaa efficacité transformateur ci natt perte yi

 May 19, 2026

 Bayil ab bataaxal

 

Q: Buñu joxee P0 ak P0 ci test yi, naka laa mëna xaymaa efficacité ci niveau de charge yu wuute?

 

A: Gaawaay η=P_génn / (P_génn + P0 + 2 × P6) × 100%, fu=facteur de charge.

Ci misaal: Trafo 10 MVA, P0=12 kW, P6=85 kW:

Diisaay natt

Sortie (kW)

P0 (kW)

2×P6 (kW)

η (%)

25%

0.25

2,500

12

5.3

99.31

50%

0.50

5,000

12

21.3

99.34

75%

0.75

7,500

12

47.8

99.21

100%

1.00

10,000

12

85.0

99.04

120%

1.20

12,000

12

122.4

98.89

Gaawaay bi gëna mag ci=√(P0 / P6)=0.376 → ~37.6% sargal.

Norm yiñ tëral ngir sakkanal kuuraŋ:

• IEC 60076-20: Klaas EEI A (gëna kawe) → D.

• Ecodesign 2019/1783: Ñaareelu dayo (2021), Ñatteelu dayo (2025–27).

• DOE 10 CFR pàcc 431: sàrt bu bees buy tàmbali liggéey ci weeru suwe 2026.

• GB 20052-2020 (Chine): Njàngale 1 (gëna kawe) → 3.

• IS 1180 (Inde): BEE 1 ba 5.

Xeetu TCO: TCO=Njëgg + A × P0 + B × P6

≈ $3,000–8,000/kW (amul njëg buñ kapitalise).

B ≈ $500–2,000/kW (jëg buñ kapitalise).

Yonnee nga laaj
Yonnee nga laaj