naka lañuy xaymaa kàttanu sistem SR ngir fiil wala test GIS?

 May 26, 2026

 Bayil ab bataaxal

 

Laaj: Dama wara saytu fiil bu 220 kV, guddaayam 8 km. Ban notu SR laa soxla?

 

A: 7-jéego doxalinu dimensionnement: xam test bi laaj → xayma C → xayma L → xayma f_res → xool note yi → baamtu → jeexal.

Jéego - ci - jéego - 220 fiil kV, 8 km:

1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Duraasioŋ 60 simili.

2. C ≈ 8 km × 0,2 μF/km=1.6 μF.

3. Xalaatal 3×100 kV/2 A ci reaktër yu paralel: L{4}} H, f=24.4 Hz.

4. Courant ci 254 kV: I=V × 2πf × C=6.9 A. Waaye 3×2A → 6A ci lëmm → DU OK.

5. Yeesal ba 3×100 kV/4 A ci reactor yi: limu tollu ci I=12 A → Waaw. P_ci=254×6.9/{9}} kW.

6. Diisaay bi yépp: 3×450 kg ~1800 kg.

 

Résumé dimensionnement ngir senaario yu bari:

senaario

V_test (kV)

C (μF)

f (Hz)

Sistem biñ la xelal

Fiil de 33 kV, 3 km

48

0.6

45

60 kv/2a x1, 5 kv

110 kV, 5 km

160

1.0

24

200 kv/4a x2, 20 kv

220 kV, 8 km

254

1.6

24

300 kv/4a x3, 50 kv

400 kV, 5 km

330

1.0

48

400 kv/2a x2, 25 kv

GIS 245 kV, 10 baies

230

0.05

80

300 kv/1a x2, 5 kv

100 MVA

28

2.5

45

30 kv/5a, 10 kv

 

Fattaliku yu am solo:

• +20% marge ci tension nominal reactor. +30% marge ci nominal courant.

• Sudee P_in > 100 kW, xalaatal test sectionnel (li standard yu bari nangu).

• Q bi am mën na wàññeeku ci li ñu xayma - waajal bu baax dafay moytu gacce yi ci tool bi.

Yonnee nga laaj