Laaj: Dama wara saytu fiil bu 220 kV, guddaayam 8 km. Ban notu SR laa soxla?
A: 7-jéego doxalinu dimensionnement: xam test bi laaj → xayma C → xayma L → xayma f_res → xool note yi → baamtu → jeexal.
Jéego - ci - jéego - 220 fiil kV, 8 km:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Duraasioŋ 60 simili.
2. C ≈ 8 km × 0,2 μF/km=1.6 μF.
3. Xalaatal 3×100 kV/2 A ci reaktër yu paralel: L{4}} H, f=24.4 Hz.
4. Courant ci 254 kV: I=V × 2πf × C=6.9 A. Waaye 3×2A → 6A ci lëmm → DU OK.
5. Yeesal ba 3×100 kV/4 A ci reactor yi: limu tollu ci I=12 A → Waaw. P_ci=254×6.9/{9}} kW.
6. Diisaay bi yépp: 3×450 kg ~1800 kg.
Résumé dimensionnement ngir senaario yu bari:
|
senaario |
V_test (kV) |
C (μF) |
f (Hz) |
Sistem biñ la xelal |
|
Fiil de 33 kV, 3 km |
48 |
0.6 |
45 |
60 kv/2a x1, 5 kv |
|
110 kV, 5 km |
160 |
1.0 |
24 |
200 kv/4a x2, 20 kv |
|
220 kV, 8 km |
254 |
1.6 |
24 |
300 kv/4a x3, 50 kv |
|
400 kV, 5 km |
330 |
1.0 |
48 |
400 kv/2a x2, 25 kv |
|
GIS 245 kV, 10 baies |
230 |
0.05 |
80 |
300 kv/1a x2, 5 kv |
|
100 MVA |
28 |
2.5 |
45 |
30 kv/5a, 10 kv |
Fattaliku yu am solo:
• +20% marge ci tension nominal reactor. +30% marge ci nominal courant.
• Sudee P_in > 100 kW, xalaatal test sectionnel (li standard yu bari nangu).
• Q bi am mën na wàññeeku ci li ñu xayma - waajal bu baax dafay moytu gacce yi ci tool bi.