Laaj: Sudee setal bi wàcci ba 95% ndax ngelaw luy dugg, ndax GIS bi dina wéy di dox?
A: Dina wéy di am kuuraŋ, waaye marge de sécurité (arc quenching ak cooling) dañuy wàññeeku bu baax.
Risk yu sell bu woyof:
❶ Wàññi Arc Quenching: Air bi 100x moo gëna bon SF6 ci taxawal arc yi. CB mën na ñàkka dagg.
❷ Disipasioŋ tàngoor: Kontaminasioŋ dafay soppi densité gaz bi ak ni muy seddalee, moo waral tàngoor wi ëpp.
Norm yi (IEC 60480):
• Gaz bu bees: Lu ëpp wala lu tollu ci 99,9%.
• Gaz biy daw: Dafa wara nekk > 97%. Lu weesu 95% fàww ñu defaraat ko.
naka lañu mëna tekki niveau SO2 ak HF?
Q: Analyseur bi dafa wane 5 ppm SO2. Resultaa bu jaadu wala njuumte ci biir?
A: SO2 mooy "Alarm saxaar" ngir arc bi ci biir. Tekki ko nii:
|
Niveau SO2 |
Tekki |
Jëf |
|
< 1 ppm |
Liggéeyukaay bu jaar yoon. |
Xool bu ñuy faral di def. |
|
1 – 5 ppm |
PD bu ndaw wala coppite bu diis. |
Gaawtal diggante test bi. |
|
5 – 10 pm |
Dafa am benn sikk bu rëy. |
Saytu UHF/PD akustik. |
|
>10 ppm |
CRITIQUE ci biir. |
Saytu/setal ci saasi. |
Expert Tip: Sudee SO2 ak HF ñoom ñaar dañu yéeg, am nga ACTIVE defect buy defar asid leegi.