Transformatëru test (Reservoir bi) ngir test hipot AC - limu doon ak kañ lañu ko wara jëfandikoo

 May 27, 2026

 Bayil ab bataaxal

 

Laaj: Dama gis benn kees bu rëy bu am ay bushing ci kaw - ab transformatëru test? Kañ laa wara jëfandikoo lii ci palaasu stack reactor bi?

 

A: Waaw - trafo test biñ gëna xam mooy trafo bi yomb (220/380V dugg, 10–300 kV genn). Jumtukaay bi gëna baax ngir sargu yu ndaw, yu am kapasite bu néew lu ci melni CTs, PTs, bushings, ak fiil yu gàtt (< 25 m).

 

Kañ nga ko wara jëfandikoo:

Yaa ngi natt...

Kàttan

Test TX?

Lu tax?

CT (transformatëru courant)

50-200 pf

✅ Li gën

Tiny charge - TX daf koy dawal ci anam wu yomb

PT (transformatër bu am doole)

100 ba 500 pf

✅ Li gën

Benn sabab bi

Bushing bu ndaw

100 ba 500 pf

✅ Li gën

Resistif bu yomb

Fiil bu gàtt < 100 m

< 20 nF

✅ Baax

Courant sarse bu doy

GIS bay (disjoncteur)

5-50 nF

✅ Nangu

C bu yam - baaxna ak marge

Fiil kuuraŋ bu 5 km

1 μF+

❌ Baaxul

courant bu rëy - xoolal FAQ 5

Stator generatër

1 μF+

❌ Baaxul

Benn jafe-jafe

 

Njëg li ñuy xayma (beesu, 2025):

50 kV / 5 kVA test TX: 8 000 ba 15 000 $

100 kV / 10 kVA test TX: 20 000 $ ba 40 000 $

200 kV / 50 kva: 50 $ waaye bariwul; nit ñi dañuy soppi SR ci niveau bii

 

Fépp fuñu ko jëfandikoo: Laboratoire usine (CT/PT/mfr bushing), usine commutateur, gaaraasu defar yu ndaw.

Xalaatal: "100 kV / 10 kVA" dafay tekki ni mën na joxe 10 kVA ci sargu resistif ci 100 kV. Waaye ci fiil capacitif, courant sarse bi mën na weesu 10 kVA - doonte voltage bi war la. Noonu la #1 anam wi ndoorte yi di yàq transformatëru test yi.